Tri Guard Fire Retardant Cables

Tri Guard Cable

Tri Guard Fire Retardent Cables

  • Tri Guard Cable
  • Tri Guard Cable

TECHNICAL SPECIFICATION

3-LAYER INSULATION I HEAT RESISTANT AND FLAME RETARDANT CABLE.

Colors :

Data Chart : Cable Design Parameters

Nominal Cross Sectional Area (Sq. mm) Nominal Insulation Thickness (mm) Number *Nominal Dia. of Strands Approx. Overall Diameter (mm) Max. DC ConductorResistance at 20°C(Ω/km) Current Rating (Amps) Casing Current Rating (Amps) Concealed
0.75 0.6 24/0.2 2.3 26.0 9 8
1 0.7 14/0.3 2.7 18.1 14 13
1.5 0.7 22/0.3 3.0 12.1 18 16
2.5 0.8 36/0.3 3.7 7.41 24 20
4 0.8 56/0.3 4.1 4.95 30 26
6 0.8 84/0.3 4.6 3.30 38 33
10 1.0 140/0.3 7.0 1.91 52 45
16 1.0 126/0.3 8.1 1.21 70 60
*Conductor as per IS 8130.

APPLICATION

Suitable for wiring in all types of residential and commercial infrastructure, where fire and electrical safety is utmost important.

TECHNICAL DATA

Approvals :

IS 694 marked.

Voltage Grade :

Up to and including 1100V

Insulation :

All 3 layers of Insulation are specially formulated grade of PVC compound is capable of withstanding higher conductor temperatures with Heat Resistant and Flame retardant properties. The HR FR property retards the propagation of flame without comprising safety.

Insulation Confirmity :

IS 5831 Type C-HR 1050C, FR 700C.

Marking :

The cables are printed with marking of "VIHAN TRI Guard FR".

Packing :

90 mtr. coil is packed in "STACKPAK" upto 4.0 sq.mm with protective cartons. Project coils of 180 mtr. also available

PROPERTIES

Limited Oxygen Index Test as per IS 10810 P-58 - > 29%

Limited Temp. Index Test as Per IS 10810 P-64 - >250°C